Power loss assessment and reduction in transmission line: case study of Rulindo-Gabiro
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
This research focuses on analyzing and minimizing power loss in high-voltage transmission
networks, specifically on the 64 km, 110 kV Rulindo-Gabiro line from the Rwanda Energy Group
(REG). A comprehensive literature review examines the methods for assessing bulk transmission
capacity and quantifying energy losses. Key issues include calculating the energy lost during
electrical transmission across the grid and identifying technological measures to reduce these
losses.
The study analyse the energy losses in the transmission line based on actual data collected from
the site. Using ETAP-PowerStation for system modeling, a single-line diagram of the existing
network was developed, followed by load flow analysis, incorporating peak loads from REG. This
analysis calculates total peak capacity loss across various voltage levels and identifies loss
contributions from line and transformer components. The impact of load and line length variations
on transmission losses is also examined. The "Loss Factor " is used to estimate annual average
power loss, translating peak loss values from load flow analysis into annual energy loss figures.
This approach is detailed in the literature section, with analyses by employing this methodology.
Efficiency improvements for REG's grid are explored, applying industry-standard loss-reduction
methods, including line double circuiting, nominal voltage uprating, and reactive power
compensation. Lines identified for potential upgrades were evaluated based on power dissipation.
For double circuiting, high-loss lines at 110 kV were prioritized, while voltage uprating targets
included select levels. Reactive power compensation was applied selectively to enhance voltage
profiles across the grid.
The study quantifies the annual energy savings from each loss-reduction approach, presenting these
in terms of financial gains. Conclusions and recommendations for optimizing the Rulindo-Gabiro
line are provided. The study found initial power losses of 195.8 kW (1.23%).
The introduction of a double-circuit transmission line significantly reduced active power losses
from 195.8 kW to 129 kW, representing an improvement of 34.11%. Similarly, reconductoring the
transmission line using twin conductors decreased losses to 137.8 kW, marking a 29.62%
Page v of 68
enhancement in efficiency from actuary values. Additionally, reactive power compensation
through the installation of capacitor banks improved the power factor from 0.78 to 0.92 and reduced
active power losses from 186.22 kW to 139.78 kW, marking a 24.93%, which subsequently
reduced reactive power losses and improved overall power quality. These upgrades also improved
voltage stability, reducing the voltage drop from 1.63% to 1.27%.